These regulations are in force until 1 January 2027, and the text of their successors had not yet been published on 25 November 2026. The result of the inspection is two reports: on measurements and on contact connections.
The electrical installation inspection once every 10 years: what it includes
Point 56 of Regulation No. 238 applies to the electrical installation, including earthing and lightning protection devices. The inspection must be carried out regardless of the form of ownership of the property, so for a flat, a private house, an apartment building and a business building.
| Part | What has to be tested | Document |
|---|---|---|
| Measurements (point 57) | Insulation resistance, total impedance of the phase-neutral loop, earthing installation resistance, earthing conductor continuity, lightning protection system | Test report, Annex 6 |
| Contact connections (point 58) | Quality of contact connections with a thermal camera in junction boxes, distribution boards and at protective device locations | Test report, Annex 7 |
Checked on 25 November 2026: Cabinet Regulation No. 238 of 19 April 2016 “Fire Safety Regulations”, points 54–58, likumi.lv/ta/id/281646. In force until 1 January 2027, repealed on 2 January 2027.
Intervals: 10 years, 2 years and 1 year
For an ordinary flat, house or office the interval is once every 10 years. If there is an explosive environment on the property or site, the inspection must be carried out once every two years, and in a chemically aggressive environment once a year. Which environment your property has follows from its activity; if you are not sure, write in the form what goes on at the property.
The ten-year interval should not be treated as a permanent law. Regulation No. 238 is repealed on 2 January 2027, and the new regulations may change it. If you are planning the next routine electrical installation inspection in 2027, check the text of the new regulations on likumi.lv.
Who can carry out the periodic inspection
Regulation No. 238 does not name a construction specialist’s certificate for the person carrying out the inspection. However, the report in Annex 6 comes with a copy of the electrical safety group card of the person doing the work, a copy of the instrument’s calibration or verification certificate and the electrical installation diagram (points 1.1–1.3 of the notes to the annex). The documents are prepared and signed by a certified electrical specialist.
What to do before and after the inspection
- Find the previous report It shows when the inspection was last carried out and which distribution boards were tested.
- Describe the property in the form Address, type of property, approximate floor area, number of distribution boards, whether there is lightning protection.
- Site visit A visit to the property costs €40. After it we tell you which measurements are needed and quote the price.
- Measurements and thermal camera The measurements and the thermal camera inspection are carried out on one occasion, as point 58 requires.
- Shortcomings If a result does not meet the standard, it is recorded in the report as a non-conformity. An electrician puts the shortcoming right, for example electrician services in Riga, and then the measurement is repeated.
What to prepare for the periodic inspection
If there is no previous report, write that in the form; this inspection will then be a new reference point. Access is needed to all distribution boards, the junction boxes that are accessible, and the earthing and lightning protection points. For the thermal camera inspection the equipment has to be running in normal mode. During the measurements some circuits will be without power, so at a business agree a time when you can afford that.
What periodic electrical installation testing costs
- Electrical installation measurements and report for a flat: from €170
- Measurements and documentation for putting a private house into use: from €230
- Site visit: €40
Prices cover the electrician’s work and the documents. Sadales tīkls and building authority fees are separate. For businesses and apartment buildings we quote the price after the site visit, because it depends on the floor area, the number of distribution boards and circuits, lightning protection and the scope of the thermal camera inspection.
Sources
- Cabinet Regulation No. 238 “Fire Safety Regulations”, points 56–58, in force until 1 January 2027 checked 25 November 2026